Float & Thermostatic Steam Traps

Series 2000 F&T VAC-30 PSIG

Return to VAC-30 PSIG Description Page

Download PDF

Materials

Part Description
Head Cast Iron, ASTM-A278 Class 30
Body Cast Iron, ASTM-A278 Class 30
Bolting Steel, Grade 5
Gaskets Non-Asbestos Fiber
Float Stainless Steel
Plug Stainless Steel
Seat Brass, 15#; Stainless Steel, 30#

Engineering Specifications

CAPACITIES (Shema) — lbs. condensate per hour

Pipe Size Model No. Pressure Differential (PSIG)
1/4 1/2 1 2 5 10 15
3/4″ FT2015-3 70 100 140 200 210 220 230
1″ FT2015-4 175 250 350 500 525 550 575
1 1/4″ FT2015-5 425 600 850 1200 1260 1320 1380
1 1/2″ FT2015-6 850 1200 1700 2400 2520 2640 2760
2″ FT2015-8 1775 2500 3550 5000 5250 5500 5750

Note on capacity: Low pressure F & T trap capacities are in accordance with standard adopted by the Steam Heating Manufacturer’s Association (SHEMA) providing for the continuous elimination of air when the trap is operating at its maximum rating. No safety factor need be applied. Actual capacities are significantly greater than the SHEMA ratings indicate.

CAPACITIES (Gross) — lbs. condensate per hour

Pipe Size

Model No.

Pressure Differential (PSIG)
1/4 1/2 1 2 5 10 15 20 25 30
3/4″ FT2015-3 293 387 513 683 824 1050 1129
1″ FT2015-4 293 387 513 683 824 1050 1129
1 1/4″ FT2015-5 630 808 1029 1302 1722 2100 2457
1 1/2″ FT2015-6 1155 1785 2520 3465 5250 6930 7980
2″ FT2015-8 2415 2940 3780 4883 7245 9450 11445
3/4″ FT2030-3 293 387 513 683 824 1050 1129 1271 1365 1439
1″ FT2030-4 293 387 513 683 824 1050 1129 1271 1365 1439
1 1/4″ FT2030-5 394 525 725 956 1260 1575 1764 1890 1995 2100
1 1/2″ FT2030-6 1050 1365 1785 2415 3570 4830 5755 6300 6930 7350
2″ FT2030-8 1365 1890 2625 3570 5460 7140 8190 9030 9765 10500

Note on capacity: Trap capacities are based on continuous discharge at stream temperature. The published figures are the result of an extensive testing program conducted in accordance with ANSI/ASME PTC 39.1 – 1980, Condensate Removal Devices for Steam Systems at the B&J factory. Significantly greater capacities are realized when condensate temperature is below saturated steam temperature. Appropriate safety factors should be applied to these ratings.

Dimensions

(3/4″-1 1/2″ shown on left; 2″ shown on right)
Size Models A B C D Weight
3/4″ FT2015-3, FT2030-3 5 11/16 5 3 5/16 5 5/8 11 lbs.
1″ FT2015-4, FT2030-4 5 11/16 5 3 5/16 5 5/8 11 lbs.
1 1/4″ FT2015-5, FT2030-5 6 1/8 5 1/2 3 5 3/8 12 lbs.
1 1/2″ FT2015-6, FT2030-6 8 1/4 6 3 8 1/4 24 lbs.
2″ FT2015-8, FT2030-8 10 4 7/8 4 7/8 9 1/4 22 lbs.